Member Center
CE for Building
Standard for CE
Other Standard
Contact Us
TeL:(+86) 025-8658 3475
Fax:(+86) 025-8658 3457
E-mail:info@hksmartps.com
Website:http://www.hksmartps.cn
ASTM E 648: floor-covering systems using a radiant heat ener
ASTM E 648: Standard test method for critical radiant flux of floor-covering systems using a radiant heat energy source.
The Floor Radiant Panel apparatus involves a horizontally mounted floor covering test sample which receives radiant energy from a gas-air fueled radiant panel mounted above one end of the sample and inclined at an angle of 30o. The radiant panel generates a radiant flux profile along the length of the sample ranging from a maximum of 1.1 W/cm2immediately under the panel to approximately 0.1 W/cm2at the end of the test sample. A gas fired pilot burner is used to initiate the ignition in the sample. The distance the flooring system burns to extinguishment is converted to watts per square centimeter (W/cm2) and is reported as critical radiant flux (CRF). This is the minimum radiant energy a fire needs to sustain flame propagation in the flooring system. In this test, a higher number indicates a more flame-resistant system.
This test method is applied to NFPA130 floor covering part of the fire performance tests.
Test data requirements: CRF≥5kw/m2